Cable cross-section

Wire size calculator

Conservative AC/DC mm² from voltage drop and heating. Default example: 12 V DC, 5 A, 5 m one-way copper at 3% drop → 4 mm² (≈ 11 AWG).

Can be added as standalone app and used offline. Not a substitute for an electrician or national wiring rules.

System
Advanced settings Copper · 3% drop
Conductor
Voltage-drop limit

ISO 10133 extra-low voltage DC: 3% typical, 10% optional.

Recommended CSA

4 mm²

≈ 11 AWG

Voltage drop is the limiting check.

Calculation details
Conductor
copper
Nearest AWG
11 AWG (4.17 mm²)
Governing check
voltage drop
Voltage-drop size
4 mm²
Heating size
0.75 mm²
S min (calculated)
3.083 mm²
Actual ΔU
0.278 V (2.31 %)
ΔU limit
0.36 V (3 %)
Ampacity of result
35 A (tabulated)
ρ (70 °C)
22.2 mΩ·mm²/m

Method